poles description
3P + N
1P + N
3P
type of measurement
Voltage
Current
Active power
Active energy
device application
Sub billing
Partial meter
accuracy class
Active energy : class 1 according to IEC 62053-21
Active energy : class B according to EN 50470-3
Active energy : class 1 according to IEC 61557-12
analogue input type
Direct input
[In] rated current 63 A
rated voltage
100...277 V
173...480 V
network frequency
60 Hz
50 Hz
technology type
Electronic
display type
LCD display
sampling rate
32 samples/cycle
measurement current
0...63 A
maximum value measured
99999999.9 kWh
communication port protocol
Modbus RTU 9.6, 19.2 and 38.4 kbauds even/odd or none
communication port support
Screw terminal block : RS485
local signalling
Power ON : indicator light (green)
Accuracy checking : flashing LED (yellow)
Communications are active on the Modbus port (Modbus) : indicator light (yellow)
number of inputs
0
number of outputs
0
mounting mode
Clip-on
mounting support
DIN rail
connections - terminals
Screw terminals 16 mm²
overvoltage category
III
standards
IEC 61010
IEC 62053-21
IEC 62053-23
UL 61010-1
IEC 61557-12
IEC 61036
product certifications
UL
EAC (sub-meter)
CE - IEC 61010 (safety)
CE - IEC 61326-1 (EMC)
CULus - ANSI C12.20 (sub-meter)
RCM - NMI M 6-1 (sub-meter)
CE - EN 61557-12 (power monitor)
CULus - UL 61010 (safety)
9 mm pitches 10
Width 90 mm
Height 95 mm
Depth 69 mm
Offer Sustainability