PLC Board Microcontroller PLC Industrial Control Panels fx2n-20MR Download / Monitoring
PLC board power supply 24VDC, select the type of Mitsubishi FX2N.
Input: 12 points
Output: 8 points
Maximum memory capacity: 8,000 steps.
Can be directly used Mitsubishi programming software GX Developer (7.08 - 8.52) Programming Download debug monitoring.
http://www.hisofttest.com/
Special software components:
M8000 (operation monitoring contact) While M8001 (operation monitoring anti-contact).
M8002 (initialize pulse contacts), M8003 (initialize pulse anti-contact).
M8004 (error indication contact).
M8011 (10 ms clock pulse), M8012 (100 ms clock pulse), M8013 (1 second clock pulse), M8014 (1 clock pulse).
M8020 (zero flag), M8021 (borrow flag), M8022 is (carry flag).
The M8029 (instruction execution marks the end of).
M8033 (memory to maintain contact).
M8034 (disables the output contacts).
M8200-M8203 (C200-C203 counting direction).
Counting direction of the M8235 (C235).
D8000 (monitoring timer is set value).
D8012 (the maximum scan time).
D8140 (Y0 pulse output count register)
M8031 --- communication status indicator relay. Turned that are communicating. Disconnect means that there is no communication.
M8032 is new key indicator relay. Turned D32 there are new key. Button for each operation, the M8032 is turned on. Reading the After you have finished setting up the key value, please put M8032 reset.
Constant support:
K range: -32768-32767 or 0-65535; H range :0-FFFFH.
http://www.hisofttest.com/